Although the mid-deep ground source heat pump could be more excellent for heating compared to other heat pumps, whose well depth is usually 2000–4000 m underground, the references on it is far fewer than the market demand to apply it more. To facility the application of the mid-deep ground source heat pump and the heating problem solution to transform the coal-boiler used in a Logistics Park of Lanzhou city, firstly, this paper established a three-dimensional numerical model of mid-deep ground source heat exchanger, and analyzed the effects of well flow, diameter and depth on heat pump performance with the help of Fluent software. And then, the heating source renovation to mid-deep ground source heat pump was carried out and the test funded by the local government was followed from February 1, 2018 to March 31, 2018. It is concluded that the numerical analysis is reasonable and the heating system is effective and reliable, whose average COP (coefficient of performance) and cumulative power consumption is 3.47 and 67 727 kWh respectively during the test period.
[1] Bulmez A.M., Ciofoaia V., Năstase G., et al., An experimental work on the performance of a solar-assisted ground-coupled heat pump using a horizontal ground heat exchanger. Renewable Energy, 2022, 183: 849–865.
[2] Tang F., Nowamooz H., Outlet temperatures of a slinky-type horizontal ground heat exchanger with the atmosphere-soil interaction. Renewable Energy, 2020, 146: 705–718.
[3] Chen J., Gong H., Bao X., et al., Study on the insulation performance of vertical double-U buried tube heat exchanger in Chongqing area. Journal of Hunan University, 2014, 41: 116–122. (in Chinese)
[4] Zhang N., Weng L., Chen J., A comparison of different heat pump air conditioning technologies. Refrigeration, Air Conditioning and Electrical Machinery, 2010, 31: 12–15. (in Chinese)
[5] Liu Z., Xu W., Qian C., et al., Investigation on the feasibility and performance of ground source heat pump (GSHP) in three cities in cold climate zone, China. Renewable Energy, 2015, 84: 89–96.
[6] Sarbu I., Sebarchievici C., General review of ground-source heat pump systems for heating and cooling of buildings. Energy and Buildings, 2014, 70: 441–454.
[7] Yuan Y., Cao X., Sun L., et al., Ground source heat pump system: A review of simulation in China. Renewable and Sustainable Energy Reviews, 2012, 16: 6814–6822.
[8] Bär K., Rühaak W., Welsch B., et al., Seasonal high temperature heat storage with medium deep borehole heat exchangers. Energy Procedia, 2015, 76: 351–360.
[9] Wang Z., Li G., Wang F., et al., Techno-economic evaluation of a frost-free air source heat pump water heater. Sustainable Cities and Society, 2020, 57: 102102.
[10] Li X., Zhao J., Zhou Q., Inner heat source model with heat and moisture transfer in soil around the underground heat exchanger. Applied Thermal Engineering, 2005, 25: 1565–1577.
[11] Mei V.C., Fischer S.K., Vertical concentric-tube ground-coupled heat exchangers. Ashrae Transactions, 1983, 89: 11435.
[12] Wang Z., Wang F., Liu J., et al., Field test and numerical investigation on the heat transfer characteristics and optimal design of the heat exchangers of a deep borehole ground source heat pump system. Energy Conversion and Management, 2017, 153: 603–615.
[13] Cullin J.R., Spitler J.D., Montagud C., et al., Validation of vertical ground heat exchanger design methodologies. Science and Technology for the Built Environment, 2015, 21: 137–149.
[14] Liu J., Wang F., Cai W., et al., Numerical investigation on the effects of geological parameters and layered subsurface on the thermal performance of medium-deep borehole heat exchanger. Renewable Energy, 2020, 149: 384–399.
[15] Renaud T., Verdin P., Falcone G., Numerical simulation of a deep borehole heat exchanger in the Krafla geothermal system. International Journal of Heat and Mass Transfer, 2019, 143: 118496.
[16] Welsch B., Ruehaak W., Schulte D.O., et al., Characteristics of medium deep borehole thermal energy storage. International Journal of Energy Research, 2016, 40: 1855–1868.
[17] Le L.M., Larroque F., Dupuy A., et al., Thermal performance of a deep borehole heat exchanger: Insights from a synthetic coupled heat and flow model. Geothermics, 2015, 57: 157–172.
[18] Yost K., Valentin A., Einstein H.H., Estimating cost and time of wellbore drilling for Engineered Geothermal Systems (EGS)–Considering uncertainties. Geothermics, 2015, 53: 85–99.
[19] Koohi-Fayegh S., Rosen M.A., An analytical approach to evaluating the effect of thermal interaction of geothermal heat exchangers on ground heat pump efficiency. Energy Conversion and Management, 2014, 78: 184–192.
[20] Widiatmojo A., Gaurav S., Ishihara T., et al., Using a capillary mat as a shallow heat exchanger for a ground source heat pump system. Energy and Buildings, 2020, 209: 109684.
[21] Lv P., Optimization of non-interference geothermal energy cascade utilization system. Xi’an Shiyou University, Xi’an, China, 2019.
[22] Su C., Madani H., Palm B., et al., Spatial data assisted ground source heat pump potential analysis in China, a case of qingdao city. Energy Procedia, 2019, 158: 6099–6104.
[23] Wang J., Hu S., Parametric analysis of the performance of deep casing type buried tube heat exchangers. District Heating, 2018, 3: 1–7. (in Chinese)
[24] Liu J., Cai W., Wang F., et al., Experimental study on deep ground source heat pump system and optimization of tube well structure. Journal of Engineering Thermophysics, 2019, 40: 2143–2150. (in Chinese)